We Proudly Accept:
|

Japanese, Taiwanese and Korean Replacement Parts
|
FIBEROPTIC LEAK DETECTION (INHERENTLY SAFE)
The HPF-D040 fiberoptic leak detector is inherently safe in that
there is no circuitry at the sensing point, only light from the
associated amplifier. The amplifier would be mounted out of the
immediate sensing area. The small and narrow sensing head and bracket
are composed of chemically resistant Teflon(r) PFA material.
A detachable mounting bracket block with an integral 316SS mounting
grommet insures adequate retention while offering easy maintenance
capability. The 5 meters of cable length has a 60 micron covering
of PFA material that provides chemical protection along with field
cut-to-desired-length ability.
Quick detection of spills is adjustable via the amplifier used.
1ml of liquid typically is required to change the amplifier's state.
The fail safe design is achieved by conducting light back to the
amplifier when liquid is not present. Liquid presence or a cable
break will stop the light from being returned. Unlike the self-contained
version and competitive offerings, the customer's pan is used to
stabilize and adjust the light return when setting the amplifier.
If the sensor becomes unattached and no longer sees the pan reflection,
the output will turn off. We call this "floating head detection"
capability.
|
|
Features
and Benefits
- Sealed, Chemically Resistant Materials - 13mm
circular sensor pancake lays on bottom of semiconductor wet process
tool and detects liquid leak or spill by refraction light principle
(see illustration on this page).
- Inherently Safe - Optical light is used from
a remotely mounted fiberoptic amplifier.
- Sealed, chemically resistant materials - PFA
housing and bracket with 316SS mounting grommet.
- Quick Detection minimizing environmental impact
and messy cleanup - typically, 1ml of liquid contact with the
optical focal point will trigger the signal change. Sensitivity
is adjustable to some extent by the amplifier used.
- Fail Safe Design - Sensing light is conducted
from amplifier emitter, reflected off pan, then returned to amplifier
receiver. When liquid is present or cable breaks, amplifier changes
state.
- Floating Head Detection Capability - If the sensing
head becomes unattached from the pan, the amplifier will change
state. There is no reflective surface included in the head design.
|
| Usage
Notes |
- Handle with care because the surfaces can be
damaged easily.
- Material - Sensor Housing: PFA, Mounting Base:
PFA, Grommet: SUS316L, Fiber Cable: See "Viewed from A".
- Fiber cables can be cut with an included tool
FE-PA-F1.
- Depending on color and viscosity of the liquid,
no detection can be made.
- Do not make over-stress
on the housing by pulling the cables.
- Mounting base can be detached from the sensor
body
|
| Specifications |
| Scanning Type: |
Diffuse Scan |
| Target: |
Liquid
Note: Depending on color and viscosity
of the liquid, no detection can be made |
| Tensile Strength: |
10N max. |
| Bending Radius: |
R20mm min. |
| Operating Temperature: |
-30+70 C |
| Amplifier Unit: |
HPX-A, HPX-H, HPX-ET, HPX-NT
(Letters and numbers depend on specifications) |
RAS Machine Tool Technologies, Inc.
30 Business Technology Drive · P.O. Box 652 · Belchertown, MA 01007
· sales@rasmachinetool.com
Website Development and Maintenance by GetSet